Search Glossary

TCVN 4529:2012 Sporting facilities - Sport building - Design standard
No data was found
TCVN 4529:2012

TCVN 4529:2012 Sporting facilities – Sport building – Design standard

Foreword

TCVN 4529:2012 replaces TCVN 4529:1988.

TCVN 4529:2012 is converted from TCXDVN 289:2004 in accordance with the provisions of Clause 1, Article 69 of the Law on Standards and Technical Regulations and Point b), Clause 1, Article 7 of the Government’s Decree No. 127/2007/ND-CP dated August 1, 2007 detailing the implementation of a number of articles of the Law on Standards and Technical Regulations.

TCVN 4529:2012 is compiled by the Institute of Architecture, Urban and Rural Planning, proposed by the Ministry of Construction, appraised by the Directorate for Standards, Metrology and Quality, and promulgated by the Ministry of Science and Technology.

1. Scope of application

1.1. This standard applies to the design of new or renovated sports buildings (including teaching, training and competition buildings).

1.2. Sports buildings are used for the following sports: Basketball, volleyball, table tennis, handball, gymnastics, martial arts, wrestling, tennis, badminton, and sepak takraw.

2. Referenced documents

The following referenced documents are indispensable for the application of this standard. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

TCVN 2622, Fire protection for buildings and structures – Design requirements.

TCVN 2737, Actions and loads – Design standards.

TCVN 4205:2012, Sports facilities – Sports grounds – Design standards.

TCVN 4474, Internal plumbing – Design standard.

TCVN 4513, Internal water supply – Design standard.

TCVN 7447, Electrical installations of buildings.

TCVN 7958:2008, Protection of construction works. Termite control for new construction works.

TCVN 9835:20121), Lightning protection for construction works – Design, inspection and maintenance guidelines for systems.

TCXD 16:19862), Artificial lighting in civil works.

TCXD 29:19912), Natural lighting in civil works – Design standard;

TCXDVN 264:20022), Buildings and structures – Basic principles of construction to ensure accessibility for disabled persons.

3. General provisions

3.1. The design solution for sports buildings must ensure a rational operation chain (athletes, coaches, spectators, service staff, etc.), apply scientific and technical advances, and make use of local materials while saving precious and rare materials.

3.2. The scale of sports buildings is determined by the land area used and the capacity of the spectator stands, as specified in Table 1.

Table 1 – Land area used for sports buildings

Building FunctionLand Area Used (ha)Capacity of Spectator Stands (thousand seats)
With Spectator StandsWithout Spectator Stands
Large Medium Small Large Medium Small Large Medium Small
1. Multi-purpose sports buildingsfrom 0.8 and abovefrom 0.6 to 0.7from 0,4 đến 0,5from 0.6 to 0,7from 0.4 to 0.50.3from 3 to 4from 2 to 3from 1 to 2
2. Single-sport buildingsfrom 0.6 to 0.70.5from 0,3 to 0.4from 0.5 to 0.60.4from 0.25 to 0.3less than 4less than 3from 1 to 2
NOTE: For sports buildings with a capacity of 5,000 seats or more, it must be specified by the competent authority.

3.3. Sports buildings are divided into 2 types:

– Multi-purpose sports buildings for many sports;

– Single-sport buildings for each sport.

3.4. The classification of sports buildings is specified in Table 2.

Table 2 – Classification of sports buildings

BuildingCourt Size (m)Minimum Clear Height (m)Service Capacity (persons/session)
LengthWidth
A. Multi-purpose sports buildings for various sports
1. For organizing competitions
Large type6036≥12.5>36
4824≥12.536
4224≥12.536
Medium type3618from 9 to 1124
3018from 9 to 1124
Small type2418from 7 to 918
1815from 7 to 918
2. For teaching and training
Large type4224from 9 to 1142
Medium type3018from 7 to 932
Small type2412from 6 to 724
B. Single-sport buildings
1. For organizing competitions
Large type6032from 9 to ≥12.5>32
4224from 9 to 12.532
Medium type3618from 7 to 924
Small type2418from 6 to 718
2. For teaching and training
Large type3618from 9 to 1136
Medium type3018from 7 to 924
Small type2412from 5 to 618
C. Gymnastics buildings
1. For organizing competitions
Large type6036
Medium type42 (48)24
Small type3618
2. For teaching and training4824
NOTES:
1) In multi-purpose sports buildings used for organizing competitions:
– Large type: used for most indoor sports;
– Medium type: not used for volleyball, handball, indoor football;
– Small type: only used for badminton, table tennis.
2) For gymnastics buildings:
– Large type: competitions for both men and women at the same time, arranging 2 sets of equipment (1 set of 6 apparatuses for men, 1 set of 4 apparatuses for women), with a 1.2m high platform;
– Medium type: separate competitions for men and women, arranging 1 set of equipment, with a 1.2m high platform;
– Small type: competitions for rhythmic gymnastics, aerobic gymnastics, tumbling, 2 carpets for rhythmic gymnastics.

3.5. The number of practice and competition courts arranged in sports buildings is specified in Table 3.

Table 3 – Number of practice and competition courts in sports buildings

Dimensions in meters

Building Scale
SportNumber of CourtsCourt Usage Size (length x width)Construction Size
PracticeCompetitionLengthWidth
Large type (42 x 24)
Volleyball2118 x 92415
Basketball2128 x 153219
Table Tennis
209practice: 15 x 8, competition: 15 x 8 (14 x 7)158
Gymnastics1242 x 244224
Badminton6413.4 x 5.18 (singles court),169
   13.4 x 6.1 (doubles court)  
Tennis3123.77 x 8.23 (singles court),3519
   23.77 x 10.97 (doubles court)  
Wrestling3312 x 121212
Handball1140 x 204422
Medium type: 36 x 18
Volleyball1118 x 92415
Basketball1128 x 153219
Table Tennis124practice: 8 x 5, competition 14 x 7147
Gymnastics1136 x 184824
Badminton4313.4 x 5.18 (singles court), 169
   13.4 x 6.1 (doubles court)  
Tennis1223.77 x 8.23 (singles court),3519
   23.77 x 10.97 (doubles court)  
Wrestling3212 x 121212
Handball1140 x 204422
Small type: 24m x 12m
Table Tennis
41practice: 15 x 8, competition 14 x 7158
Badminton1113.4 x 6.1 (doubles court)169
Rhythmic Gymnastics, Aerobic Gymnastics, Tumbling11dimensions depend on practice mat  
Wrestling2112 x 121212
NOTE: For some other sports, when there is a need for indoor practice or competition, it can be selected to be suitable and corresponding to the sports specified in this table.

3.6. The grading of sports buildings is specified in Table 4.

Table 4 – Grades of sports building facilities

Grade IGrade IIGrade III
Used for training, teaching and organizing international competitions.Used for training, teaching and organizing national competitions.Used for training, teaching and organizing domestic competitions from provincial level and below.
Practice floor made of high-grade synthetic rubber, laminated wood.Practice floor made of steel wood, synthetic materials.Practice floor made of aggregate.
Equipment used meets international standards.Equipment used meets international standards.Equipment used requires general inspection.
Usage quality reaches high level, service life over 100 years, fire resistance level I or II.Usage quality reaches good level, service life from 50 to 100 years, fire resistance level III.Usage quality reaches average level, service life from 20 to 50 years, fire resistance level IV.
NOTES:
1) For grade I sports buildings, it is allowed to use a wooden practice floor but must ensure the technical requirements for international competition.
2) The fire resistance level is calculated according to the fire resistance level of the structural components of the sports building specified in Table 5.
3) Priority is given to designing high facility grades for sports buildings.

Table 5 – Fire resistance levels of structural components of sports buildings

Structural ComponentFire Resistance Duration of Structural Component (min) with Building’s Fire Resistance Level:
lllllIlVV
1. Columns, load-bearing walls, stairwell walls15012012030
2. Load-bearing components of floors60454515
3. Load-bearing components of roofs3015
4. Enclosure walls, partition walls30151515
5. Staircases60606015
4. Requirements for construction sites and general layout planning

4.1. The land for constructing sports buildings must ensure:

  • Compliance with the approved planning, having sufficient area for construction and potential for future expansion;
  • Rational use of land and urban space;
  • High and dry ground, easy drainage, convenient transportation for organizing physical training and sports activities and safe evacuation;
  • Convenience for water supply and power supply.

4.2. The service radius of sports buildings is taken as follows:

  • For urban residential units (or communes): ≤ 500 m;
  • For residential areas (districts, urban districts): ≤ 1,200 m;
  • For cities and towns: ≤ 2,000 m.

NOTE: Service radius is the distance from the farthest place of residence in the residential area to the sports facility.

4.3. Sports buildings should be arranged near other sports facilities and consider the possibility of coordination between facilities to form urban sports complexes. In that case, the construction land will be calculated according to the standard of the largest settlement.

4.4. The minimum sanitary distance for sports buildings must comply with the regulations on construction planning [1] as shown in Table 6.

Table 6 – Sanitary distance for sports buildings

Dimensions in meters

Facility NameMinimum Distance
Hospital1 000
Cemetery, landfill2 000
Factory with toxicity level I1 000
Factory with toxicity level II500
Factory with toxicity level III300
Factory with toxicity level IV100
Factory with toxicity level V50
NOTE: If the facility is located at the end of the prevailing wind direction, this distance needs to be calculated appropriately.

4.5. Around the construction site of sports buildings, a green belt should be planted to prevent wind, dust and reduce noise. The width shall not be less than 10 m. The total green area must not be less than 30% of the construction site area.

NOTES:

1) The green area includes the area of windbreak, dust protection belts and lawns.

2) For sports buildings located in park areas, the green area is taken according to the requirements of the specific architectural solution and agreed upon by the competent authority.

4.6. On the construction site, there must be evacuation routes in case of emergencies. The width of the evacuation route is calculated according to the standard of 1 m for 500 people. There must be at least 2 entrances and exits for pedestrians and 2 entrances and exits for cars and motorbikes.

4.7. The overall layout design of sports buildings should ensure a reasonable division of zones, convenient for organizing physical training and sports activities.

4.8. The orientation of sports buildings should ensure:

  • Catching the prevailing wind in summer;
  • Taking advantage of natural light to illuminate the building.

4.9. There must be a solution to arrange the traffic network in the facility so that:

  • The flows of athletes and spectators do not overlap;
  • There are separate traffic routes for storage areas and parking lots;
  • There is a gathering area for people and vehicles in front of the gate (parking lot). The standard area is 0.3 m2/seat based on the number of seats in the spectator stands;
  • Ensuring convenient traffic for firefighting vehicles. Having safe and timely evacuation routes in case of emergencies.

NOTE: The traffic arrangement solution must take into account the usage and accessibility needs of people with disabilities. Design requirements are according to TCXDVN 264:2002.

4.10. Reasonable traffic routes must be arranged, without overlapping the routes of athletes with the routes of spectators. Traffic routes for storage areas and parking lots must be arranged separately. The calculation criteria for parking lot area are taken as follows:

  • Cars: 25 m2/vehicle;
  • Motorcycles, motorbikes: 3.0 m2/vehicle;
  • Bicycles: 0.9 m2/vehicle;

4.11. The outer edge adjacent to the road of sports buildings must be at least 15 m away from the boundary line for regular traffic roads and 50 m for high-density traffic roads.

5. Building content and design solutions

5.1. The rational operation chain of athletes must follow the sequence:

Lobby (with cloakroom) Changing rooms (separate for men and women) Showers and toilets Practice and competition courts.

5.2. When designing sports buildings, the following regulations must be followed:

  • Ensuring the correct dimensions of the practice courts as specified in Table 7;
  • For multi-purpose sports buildings, the practice courts must be arranged according to the correct dimensions specified for each sport in TCVN 4205:2012.

Table 7 – Dimensions of practice courts in sports buildings

Dimensions in meters

SportUsage DimensionsNumber of People per SessionNotes
LengthWidthMinimum Clear Height
1. Volleyball1891324If arranged indoors with spectators, the distance from the end lines to the spectator seats must be 8 m and 5 m along the two side lines. International competition halls must have a clear height of not less than 12.5 m.
2. Basketball2815924The distance from the boundary lines to the spectator seats shall not be less than 2 m.
2614  
2413  
3. Handball4020924The standard length of the training floor ranges from 38 m to 44 m.
4. Badminton    If 2 courts are arranged side by side, the minimum distance between them is 4 m
– Singles13.45.18từ 11 đến 12.512
– Doubles13.46.10
5. Table Tennis7.754.548 people/1 tableFor national and international competitions, the court dimensions for each side are 14 m x 7 m
6. Tennis    If multiple courts are arranged side by side, the distance between the two side lines is 5 m.
a. Court for organizing competitions    
– Singles23.778.23≥ 9 
– Doubles23.7710.97≥ 912
b. Courts for training1612≥ 916Courts must have surrounding nets with a height of 3 m.
7. Gymnastics    The height of 8 m applies to both artistic and rhythmic gymnastics
– Organizing international competitions60368 
– For 1 set of specialized men’s equipment (horizontal bar, parallel bars, rings, pommel horse, vault) or women’s equipment (uneven bars, balance beam, vault) along with a 12 m x 12 m gymnastics mat3618824The clear height of the halls can be reduced at the following positions:
– Horizontal bar 5.5 m;
– Parallel bars 5.0 m;- Vault 4.5 m;
– Pommel horse 3.5 m;
In a multipurpose sports hall with specialized competition equipment on a platform (1.2 m high), the competition floor dimensions shall not be less than 48 m x 24 m.
– For one specialized equipment, expanded with a 12 m x 12 m gymnastics mat3618628 
– For two sets of men’s and women’s specialized equipment along with a 12 m x 12 m gymnastics mat4824732 
8. Boxing    A 6 m x 6 m ring is arranged in a national competition hall with spectators.
– For 1 ring of 6 m x 6 m and 10 judges’ tables1812618
– For 2 rings of 6 m x 6 m and judges’ tables2414626
9. Wrestling    – Cổ điển, tự do và săm bô cho 1 thảm vật đường kính 9 m hoặc 2 thảm vật đường kính 7 m
– Greco-Roman, freestyle and sambo for 1 wrestling mat with a diameter of 9 m or 2 wrestling mats with a diameter of 7 m each2414512
– Greco-Roman, freestyle and sambo for 2 adjacent wrestling mats with a diameter of 9 m each3018518If the wrestling mat is placed on a 1 m high platform, the floor dimensions will be 19 m x 19 m
– Judo: 14 m x 14 m wrestling mat2414512If arranged in an indoor hall with spectators, the mat dimensions are 18 m x 18 m; if the wrestling mat is placed on a 1 m high platform, the mat dimensions are 20 m x 20 m. The safety zone between wrestling mats shall not be less than 3 m
10. Fencing: for 1 fencing strip and testing equipment2214412The width of the training floor is calculated as 5 m for 1 fencing strip plus 3 m for each additional strip. If arranged in an indoor hall with spectators, the competition floor dimensions are 22 m x 8 m (or can be 18 m x 8 m) for one fencing strip.
11. Weightlifting    If arranged in an indoor hall with spectators, the competition floor dimensions are 12 m x 12 m.
– Cho 1 bệ kích thước 4 m x 4 m và 2 bệ 3,2 m x 3,2 m và các thiết bị kiểm tra18948
– For 1 platform of 4 m x 4 m and 4 platforms of 3.2 m x 3.2 m and testing equipment2412412 
12. Dimensions of courts in sports halls    The clear height is taken as the requirement for wrestling mats
– Judo court1010 12
– Karatedo court88 12
– Taekwondo court1212 14
– Freestyle wrestling court24D:914D:9 12
– Bodybuilding1414 16
– Artistic gymnastics
– Rhythmic gymnastics
NOTE: The dimensions in the table above are taken from the structural grid dimensions of the building, taking into account the modular coordination of dimensions between building structures.

NOTE: The dimensions in the above table are taken from the coordinate axis dimensions of the building, taking into account the modular coordination of dimensions between building structures.

5.3. For multi-functional sports buildings combined with artistic performances, the size of the stage layout must ensure 24 m x 18 m.

5.4. The clear height of the competition building at the competition floor area must be suitable for the requirements of the competition sport. Outside the scope of the competition floor, the clear height can be reduced but must not be less than 3 m.

NOTE: For general teaching and training buildings, the reduction of height according to the above provisions must be approved in the technical and economic report and not affect sports activities.

5.5. The dimensions of multi-purpose sports buildings for various sports must be taken according to the sports with the largest dimensional requirements among the sports used in the building.

NOTE: For sports buildings organizing international competitions, a press conference room should be arranged.

5.6. When determining the design loads for the load-bearing structures of sports buildings, the provisions in TCVN 2737 must be followed and the following requirements must be satisfied:

  • The building floor is designed with a load of 400 daN/m2;
  • For weightlifting floors, the design must take into account the impact of weights and equipment. In this case, the force acting on the floor is taken as equivalent to a force by a 250 kg object falling from a height of 2.4 m.

5.7. Depending on the usage requirements and actual conditions, the floor of sports buildings can be designed in the following forms:

  • Floor made of synthetic rubber;
  • Elastic or semi-elastic wooden floor;
  • Aggregate floor.

NOTE: The construction of aggregate floors must comply with the provisions in TCVN 4205:2012.

5.8. The floor of sports buildings should not be designed with concrete. It is allowed to use plastic mixtures for flooring when the technical and economic conditions permit.

5.9. The surface of wooden floors must be at least 0.6 m higher than the ground. Wood used for flooring must be from group II or above and must be treated against termites in accordance with the provisions in TCVN 7958:2008.

5.10. For weightlifting, when designing the floor, the following requirements must be noted:

  • Weights are not allowed to fall directly on the floor;
  • The structure of the weightlifting floor must be independent, not connected to the structure of the building floor and must be placed directly on the ground;
  • There must be appropriate cushions to support the weights.

5.11. The interior wall surface of sports buildings should have light colors and must not be covered with flammable materials. Within a height of 1.8 m (measured from the floor), no protruding structures or recesses are allowed. Walls and doors must be flush when the doors are closed, and the door surface must be level with the wall surface.

5.12. The ceiling of sports buildings must have light colors and be resistant to ball impact. At the lighting locations, there must be safety protection devices.

5.13. Sports buildings must have at least two entrances and exits, with the width of each door not less than 2.1 m.

  • Doors open to the outside and one of the two doors must have a height of not less than 3 m;
  • Doors connecting from the sports floor to equipment rooms must have a width of not less than 1.8 m, with doors opening towards the floor;
  • For sports buildings with spectator stands, the design of doors must ensure safety requirements when evacuating people according to calculations.

NOTE: Folding doors and sliding doors should not be used in sports buildings.

5.14. Storages for sports equipment and gear must have a direct connection to the practice and competition floor. The floor level of the storage must be equal to the level of the practice or competition floor.

5.15. When designing spectator stands, the sightline from the spectator’s eye to the observation point (denoted as F) must be ensured as specified in Figure 1.

NOTE: For sports grounds without a roof or outdoor sports grounds, the value of C = 150

Dimensions in millimeters

Figure 1 – Position of observation point F

5.16. The spectator stand steps must meet the following requirements (see Figure 2):

  • The width of the step surface is not less than 750 mm;
  • The width of one seat is not less than 400 mm;
  • The height of the step is not less than 350 mm;
  • The lowest step surface of the stands must be 600 mm higher than the court surface;
  • The slope of the stands is not greater than 1:1.5.

NOTE: The seating steps on the stands must ensure the sightline from the spectator’s eye to the observation point as specified in 5.15.

Dimensions in millimeters

Figure 2 – Dimensions of seats on spectator stands

5.17. The seating on the stands must be divided into sections by aisles or stairs. The dimensions and layout of seating on the stands must meet the following requirements:

  • The height from the stand floor surface to the spectator’s eye is 1.15 m for seated spectators and 1.55 m for standing spectators;
  • The distance from the lowest step of the stands to the nearest edge of the court is 5 m;
  • In front of the lowest step, there must be a transparent railing with a height of 0.8 m. Behind the last step, there must be a solid wall with a height of at least 1.5 m.

5.18. The spectator stand area must have emergency evacuation routes and must meet the following requirements:

  • When evacuating people in two directions: no more than 50 seats per row should be arranged between the two exits;
  • When evacuating people in one direction: no more than 25 seats per row should be arranged.

NOTE: When designing stands, it is necessary to arrange aisles and seating for people with disabilities in accordance with the provisions in TCXDVN 264:2002.

5.19. Depending on the usage requirements and functions of the building, steps or seats for spectators can be designed. In multi-purpose sports buildings, it is allowed to arrange mobile-type seats placed directly on the court surface.

5.20. The distance between two longitudinal aisles on the stands must not exceed 7 steps (or 7 rows of seats). The width of the longitudinal aisle (including the depth of one seating step) is not less than 0.8 m. The height of the steps going up and down the stands and stairs must be ensured from 0.12 m to 0.17 m.

5.21. It is allowed to design balconies to be used as spectator stands in sports buildings. In this case, behind the topmost seating step of the stands, there must be a protective railing with a height of at least 1.0 m.

5.22. The railing separating the stands and the competition floor must not be lower than 0.8 m, must be ensured to be vertical, flat, and not affect the sightline of spectators in the first row of seats.

5.23. The slope of the stairs going up and down the stands must be appropriate, ensuring safety when evacuating people, and should not be folded multiple times.

5.24. At the spectator gathering points, traffic nodes must be organized.

5.25. The composition and area of rooms serving athletes are specified in Table 8.

Table 8 – Area of rooms serving athletes

Room NameArea StandardMinimum Clear Height (m)Notes
1. Lobby0.15 m2/seat. The number of seats is calculated as 105% of the service capacity2.7 
2. Cloakroom0.07 m2/seat. The number of seats is calculated as 210% of the service capacity2.1Minimum 10 m2
3. Athletes’ rest room
1.5 m2/person. The number of people is calculated as 20% of the service capacity
2.7Separate for men and women, minimum 15 m2
4. Lecture room30 m2/class. The number of classes is determined according to the specific design task.  When there are 2 or more classes, a 10 m2 storage is needed for equipment
5. Athletes’ changing rooms40 m2/room x 4 rooms2.7Separate for men and women
6. Referees’ changing rooms12 m2/room x 2 rooms2.7Separate for men and women
7. Shower room1 showerhead/10 people. The number of people is calculated as 105% of the service capacity2.1 
8. Washbasin room1 washbasin/5 people. The number of people is calculated as 105% of the service capacityfrom 2.1 to 2.7 
9. Toilet  Male to female ratio taken as 2/1
Male1 toilet + 1 urinal/30 people 
Female1 toilet + 1 urinal/30 people 
10. Washing area0.5 m2/ 5 people2.1 
11. Medical roomfrom 16 m2 to 20 m22.7 
12. Canteen (including sales area and storage)from 20 m2 to 40 m22.7for small sports buildings
from 45 m2 to 60 m2for medium sports buildings
from 65 m2 to 80 m2for large sports buildings
NOTES:
1) Sports medicine rooms, supplementary training rooms, and technical rooms for electricity, water, ventilation, etc. are designed according to the specific feasibility project report.
2) In the athletes’ changing rooms, enclosed design including a toilet and shower room should be implemented.

5.26. The width of walkways in changing rooms must not be less than:

  • 1 m for main walkways;
  • 1 m for the distance between rows of seats and parallel walls;
  • 1.5 m for the distance between facing rows of seats.

5.27. The components and areas of spectator service rooms are specified in Table 9.

Table 9 – Areas of spectator service rooms

Room nameArea standardNotes
1. Lobby0.15 m2/person2 
2. Rest room (hallway)0.40 m2/person (500-seat grandstand) 
0.35 m2/person (500 to 1,000-seat grandstand) 
0.30 m2/person (over 1,000-seat grandstand) 
3. Ticket office1.50 m2/ticket window serving 500 people 
4. Canteen1.50 m2/sales point serving 500 people can be located outside the building but no further than 50 m
5. Men’s toilet1 toilet + 1 handwash basin/500 people1 urinal/75 peoplemale/female ratio is 3/1 if no specific requirements
6. Women’s toilet

5.28. The areas of canteen and storage rooms depend on the number of spectators as specified in Table 10.

Table 10 – Areas of canteen and storage rooms

Sales points, places123456
Canteen area, m227486888110132
Storage area, m291216202530
NOTES:
1) One sales point serves 500 people.
2) Sales points are evenly distributed for grandstands.

5.29. The components and areas of administrative management rooms are specified in Table 11.

Table 11 – Areas of administrative management rooms

Room nameArea standardNotes
1. Office4 m2/employeedepending on the scale of the building
2. Director’s roomfrom 12 m2 to 18 m2 
3. Security guard duty roomfrom 6 m2 to 8 m2If arranging night duty, the area standard is 9 m2/security guard
4. Technical duty roomfrom 10 m2 to 12 m2Separate for men/women and only arranged in medium and large sports facilities
5. Service staff rest room2 x 12 m2Separate for men/women
6. Cleaning equipment storagefrom 2 m2/toilet area to 4 m2/toilet area 
6. Technical system design requirements
6.1. Electrical – lightning protection design requirements

6.1.1. For class II and above sports facilities, information systems, electric meters, electronic boards and television systems must be designed.

6.1.2. The design and installation of electrical equipment and wiring must comply with the provisions in TCVN 7447.

6.1.3. Sports facilities must be designed with lightning protection according to the provisions in TCVN 9835:2012.

6.2. Lighting design requirements

6.2.1. Natural lighting

6.2.1.1. Natural light must be fully utilized for lighting sports facilities. Warm-up rooms, supplementary training rooms, medical rooms, classrooms, offices and repair workshops need direct natural lighting. Side lighting, top lighting or a combination of both can be used in accordance with the provisions of TCXD 29:1991. Sports facilities with grandstands need to be designed with both natural and artificial lighting.

6.2.1.2. The area of light-receiving windows of sports facilities and rooms is taken from 1/5 to 1/6 of the floor area. The minimum uniformity for natural lighting is 1/2. For teaching and training facilities, light-receiving windows are allowed to be arranged on the roof.

6.2.1.3. When designing natural light-receiving windows, the following provisions must be complied with:

  • Do not open windows facing West or Southwest;
  • The bottom edge of the windows must be at least 2 m higher than the floor;
  • Do not arrange windows at the 2 ends of the longitudinal axis of the sports facility.

NOTES:

1) When necessary, supplementary lighting must be provided to ensure the required illuminance. It is allowed to open light-receiving windows at the 2 ends of the longitudinal axis of the sports facility, but the bottom edge of the windows must be at least 4.5 m higher than the floor. For sports facilities with low height requirements, it is allowed to change the height of the light-receiving windows.

2) In case windows must be opened facing West or Southwest, measures must be taken to prevent direct sunlight from entering the facility.

6.2.2. Artificial lighting

6.2.2.1. Artificial lighting for sports facilities must comply with the provisions in TCXD 16:1986 to ensure the necessary requirements for physical training and sports activities, safe evacuation in case of incidents, and building protection at night.

6.2.2.2. The power supply for sports facilities is specified as follows:

  • For class II and above facilities: there must be 2 supply sources;
  • For class III facilities: only one supply source directly taken from the overhead power line.

6.2.2.3. For sports facilities used for volleyball, basketball, tennis, lights must not be placed on the walls at the 2 ends of the longitudinal axis of the building (except for reflected lights). If necessary, the inclination angle of the light beam to the horizontal plane must not be less than 65°.

6.2.2.4. The lighting direction must not be opposite to the running direction of the athletes; it is best to arrange the lighting source from top to bottom.

6.2.2.5. The use of lamp types is specified as follows:

  • For work lighting: all types of incandescent and fluorescent lamps with a spectrum close to daylight are allowed to be used;
  • For emergency lighting: only incandescent lamps are used and arranged on the exits of sports facilities with 100 people or more;
  • The lamp types used in sports facilities must have protective grids to ensure the safety of athletes and spectators.

6.2.2.6. When designing artificial lighting, the following requirements must be met:

  • Illuminance;
  • Uniformity;
  • Reduction of glare and light beam analysis;
  • No creation of weak shadows;
  • Correct color rendering.

6.2.2.7. The illuminance and lamp mounting height in sports facilities are specified in Table 12.

Table 12 – Illuminance and lamp mounting height in sports facilities

SportMinimum illuminance on planes luxMinimum lamp mounting height m
ĐứngNgang
1. Volleyball   
– International competitions, major domestic competitionsfrom 300 to 40075from 11 to 12.5
– Mass competitions, recreational activitiesfrom 150 to 20050from 9 to 11
– Training, teaching, practicefrom 100 to 15050from 8 to 10
2. Basketball, handball   
– International competitions, major domestic competitionsfrom 250 to 3008511
– Mass competitions, recreational activities, and serving training, teaching200709
3. Tennis   
– International competitions, major domestic competitions20075from 8 to 9
– Mass competitions, recreational activities, and serving training, teaching150508
4. Badminton, shuttlecock   
– International competitions, major domestic competitions25080from 7 to 9
– Mass competitions, recreational activities, and serving training, teachingfrom 100 to 15070from 7 to 9
5. Table tennis   
– International competitions, major domestic competitionsfrom 100 to 150400from 4 to 6
– Mass competitions, recreational activities, and serving training, teaching300from 4 to 6
6. Gymnastics   
– International competitions, major domestic competitions3001007
– Mass competitions, recreational activities25075from 6 to 7
– Training, teaching20070from 6 to 7
7. Wrestling, boxing   
– International competitions, major domestic competitions250706
– Mass competitions, recreational activities, and serving training, teaching150606
8. Weightlifting, fencing   
– International competitions, major domestic competitions200606
– Mass competitions, recreational activities, and serving training, teachin150606

6.2.2.8. The lighting control system in sports facilities must be centrally arranged in one place, with signs for each group of lights and equipment. The location of the electrical panel must ensure safe and convenient use.

6.2.2.9. For class I sports facilities, emergency lighting can be designed with illuminance on the working plane not less than 5% of the working lighting illuminance value. The illuminance of lighting on the grandstand should not exceed 30% of the working lighting illuminance value.

6.2.2.10. Limit the use of incandescent lamps for lighting in physical training and sports activity areas.

6.2.2.11. The distributed and protective lighting system must be independent of the working lighting system. At traffic intersections and turning points on evacuation routes, lights and signage must be arranged.

6.2.2.12. The minimum illuminance of distributed lighting must not be less than 5 lux indoors and 3 lux outdoors.

6.3. Ventilation design requirements

6.3.1. Sports facilities must have direct natural ventilation. If necessary, artificial ventilation systems must be designed for the following rooms:

  • Supplementary training rooms;
  • Shower rooms;
  • Chemical storage (if any);
  • Mechanical equipment rooms.

NOTE: If required, a central air conditioning system can be designed.

6.3.2. The number of air changes in rooms of sports facilities with ventilation system design is specified in Table 13.

Table 13 – Number of air changes in sports facility rooms

Room nameNumber of air changes
ExhaustSupply
1. Sports hall floor, training roomAccording to calculation but not less than 80 m3/hour per practicing person and more than 20 m3/hour per spectator
2. Shower room, changing room510
3. Massage room23
4. Toilet room2100 m3/hour per toilet and urinal
5. Mechanical equipment room23
6. Storage rooms of all types512
6.4. Sound design requirements

When designing sound for sports facilities, the following requirements must be met:

  • Use appropriate materials to reduce noise, prevent acoustic chaos, interference, etc.
  • Open sound outlets according to calculations and should be combined with natural light windows;
  • Noise level in sports facilities must not exceed 90 dB (for class II and above facilities).
6.5. Water supply and drainage design requirements

6.5.1. When designing water supply and drainage systems for sports facilities, the provisions in TCVN 4513 and TCVN 4474 should be followed.

6.5.2. The water supply for sports facilities must be taken from the general water supply system. Local water supply systems are only allowed to be designed when approved by competent authorities. In places without an urban water supply system, it is allowed to utilize natural water sources to supply sports facilities, but they must be treated by sedimentation and filtration methods.

6.5.3. The water use standards for sports facilities are specified in Table 14.

Table 14 – Water use standards in sports facilities

Water usersWater use standards
1. Athletesfrom 50 liters/day/athlete to 100 liters/day/athlete
2. Spectatorsfrom 10 liters/day/seat to 15 liters/day/seat
3. Greenery, lawn wateringfrom 3 liters/m2 per watering

6.5.4. The calculated water flow rate, direct connecting pipe diameter, equivalent length and simultaneous usage ratio of sanitary equipment are specified in Table 15.

Table 15 – Calculated water flow rates of sanitary equipment

Equipment nameFlow rate l/sEquivalent length m/sDirect connecting pipe diameter mmSimultaneous usage ratio %
1. Handwash basin0.0700.33from 10 to 1580
2. Toilet bowl0.1000.50from 10 to 1570
3. Wall-hung urinal0.0350.17from 10 to 15100
4. Each meter of urinal trough flushing pipe0.0600.30from 10 to 15100
5. Shower head0.2001.0015100
6. Inlet valve to foot washing basin0.0700.35from 10 to 15100
6.6. Fire protection requirements

6.6.1. The fire resistance level of sports facilities is determined according to the provisions in TCVN 2622. The minimum fire resistance level of fire-resistant structures on grandstands must be equal to the fire resistance level of the sports facility.

6.6.2. When arranging rooms under grandstands with fire resistance level less than or equal to II, they must be separated from the grandstands by structures made of non-combustible or fire-retardant materials and must ensure a fire resistance limit of not less than 60 minutes.

6.6.3. The number of spectators arranged to evacuate through one exit must not exceed 500 people. The width of spectator dispersal routes and entrances/exits of sports facilities is specified in Table 16 and must comply with fire safety regulations for buildings and structures [2].

6.6.4. The maximum length of spectator dispersal routes (from the farthest seat position to the nearest exit) must not exceed:

  • 12 m for horizontal dispersal;
  • 23 m for downward dispersal;
  • 20 m for upward dispersal by stairs.

Table 16 – Width of spectator dispersal routes

Building volume including grandstands 1 000 m3Fire resistance levelNumber of people/1 m width of dispersal route
Up to 5from l to ll120
lll100
Over 5 to 10from l to ll170
lll140
Over 10 to 20from l to ll220
lll180
Over 20 to 40from l to ll280
lll220
Over 40from l to ll320
lll250
NOTES:
1) When dispersing spectators upward by stairs, calculate with 60% of the number of people specified in the table. When dispersing downward: calculate with 70%. When passing through doors: calculate with 80%.
2) For horizontal walkways and stairs, the width of spectator dispersal routes must not be less than 1.0 m; for indoor doors not less than 1.2 m, and for outdoor doors not less than 1.5 m.

6.6.5. For sports facilities with grandstands or sports facilities with a volume greater than 5,000 m3 (regardless of whether they have grandstands or not), fire water supply must be designed according to TCVN 2622.

6.6.6. Sports facilities with a volume from 5,000 m3 to 25,000 m3 must have one fire hydrant with a flow rate of 2.5 l/s; for sports facilities with a volume over 25,000 m3, two fire hydrants with a flow rate of 2.5 l/s must be installed.

REFERENCE LIST

[1] QCXDVN 01:2018/BXD, National Technical Regulation – Construction Planning.

[2] QCVN 06:2010/BXD, National Technical Regulation – Fire Safety for Buildings and Structures;


1) TCVN to be issued

2) TCXDVN and TCXD are being converted to TCVN